working temperature : -10℃~+70℃
Current Range : ±70A
Band Width : 100kHz
Bidirectional Current Detection : Support
Description : ±70A Current Sensors RoHS
Mfr. Part # : LT58-S7/SP1
Model Number : LT58-S7/SP1
The LT 58-S7/SP1 is an insulated current sensor utilizing the Hall effect principle for measuring DC, AC, and pulsed currents. It offers high accuracy, excellent linearity, low temperature drift, and a wide frequency bandwidth, making it suitable for various industrial applications. The sensor features a closed-loop (compensated) design and is housed in a UL 94-V0 insulating casing.
| Parameter | Description | Value | Unit |
| Product Name | Current Sensor | LT 58-S7/SP1 | |
| Primary Rated RMS Current (IPN) | Primary rated effective value current | 50 | A |
| Primary Current Measurement Range (IP) | Primary current, measurement range | 0 .. 70 | A |
| Measuring Resistance (RM) | @ 12 V | 0 .. 140 | |
| @ 15 V | 0 .. 200 | ||
| Secondary Rated RMS Current (ISN) | Secondary rated effective value current | 50 | mA |
| Conversion Ratio (KN) | Conversion rate | 1 : 1000 | |
| Supply Voltage (VC) | Power voltage ( 5 %) | 12 .. 15 | V |
| Current Consumption (IC) | Current consumption @ 12V | 28 + IS | mA |
| AC Insulation Test Voltage (Vd) | Effective voltage for AC insulation detection (50 Hz, 1 min) | 6 | kV |
| Overall Accuracy (XG) | Total accuracy @ IPN, TA = 25C | 0.8 | % |
| Linearity (L) | Linearity | < 0.2 | % |
| Zero Offset Current (IO) | Zero offset current @ TA = 25C | 0.2 | mA |
| Magnetic Offset Current (IOM) | Magnetic offset current @ IP = 0, overload through IPN | 0.1 | mA |
| Offset Current Temperature Drift (IOT) | (- 10C .. + 70C) | 0.35 | mA |
| 0.64 | mA | ||
| Response Time (tra) | Reaction time @ 10 % of IP max | < 500 | ns |
| Response Time (tr) | Response time @ 90 % of IP max | < 1 | s |
| di/dt Following Accuracy | di/dt following accuracy | > 100 | A/s |
| Bandwidth (f) | Bandwidth (- 3 dB) | DC .. 100 | kHz |
| Operating Temperature (TA) | Environment operating temperature | - 10 .. + 70 | C |
| Storage Temperature (TS) | Environment storage temperature | - 25 .. + 80 | C |
| Secondary Coil Resistance (RS) | Secondary coil resistance @ TA = 70C | 11 | |
| Mass | Mass | 68 | g |
| Primary Conductor Temperature Limit | Primary conductor temperature not to exceed | 100 | C |
|
|
Industrial current sensor LEM LT58-S7SP1 with compensated closed loop design and UL 94V0 insulated casing Images |