| Sign In | Join Free | My infospaceinc.com |
|
Description : Current Sensors RoHS
Mfr. Part # : DK 200 B420 B
Model Number : DK 200 B420 B
The LEM DK-B420 B is a split-core DC current transducer designed for electronic measurement with galvanic separation between primary and secondary circuits. It features a 4-20 mA DC output current proportional to the measured current, offering DC bipolar measurement (magnitude and direction), three jumper-selectable ranges, and panel mounting. Key advantages include a large aperture, extended measuring range, high insulation, easy installation, and no insertion loss. Applications span renewable energies, power supplies, battery banks, and electric heating elements.
| Primary Nominal Current (IPN) | Output Current (IOUT) | Types | RoHS Date Code | Supply Voltage (UC) | Max Load Resistance (RL) | Output Current Limitation (ISL) | Max Current Consumption (IC) | Accuracy @ IPN, TA = 25 C | Linearity Error | Step Response Time (tr) | Frequency Bandwidth (BW) | Ambient Operating Temp. (TA) | Ambient Storage Temp. (TS) | Mass | Protection Degree | Insulation Test Voltage (Ud Rms) | Rated Insulation Voltage (UB) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 50, 75, 100 A | 4-20 mA DC | DK 100 B420 B | August 2009 | 20-45 V DC | 650 | 23 mA | 100 mA | 1 % of FS | 0.75 % of IPN | < 100 ms | DC Hz | -20 .. +50 C | -20 .. +85 C | 120 g | IP 20 | 3 kV | 150 V |
| 100, 150, 200 A | 4-20 mA DC | DK 200 B420 B | August 2009 | 20-45 V DC | 650 | 23 mA | 100 mA | 1 % of FS | 0.75 % of IPN | < 100 ms | DC Hz | -20 .. +50 C | -20 .. +85 C | 120 g | IP 20 | 3 kV | 150 V |
|
|
Split core DC current transducer LEM DK 200 B420 B with galvanic isolation and 4 20 mA output current Images |